Robinair RG3 refrigerant recovery machine is used to recover both liquid & vapour refrigerants from systems before servicing them. This refrigerant recovery unit can recover CFC, HFC & HCFC refrigerants and store them in a 30 / 50-lb DOT-approved cylinder. It comes with compatible hoses, a manifold gauge set & a recovery cylinder.
Features:
- Robinair RG3 refrigerant recovery machine is a compact & lightweight unit with an oilless compressor & simple 2-valve controls for easy vapour and liquid refrigerant recovery.
- It is equipped with a safety switch to shut down the unit automatically when the pressure goes beyond 550 psi.
- The unit comes with a filter screen placed behind the inlet fitting. Users should clean the screen after every use.
- It is equipped with a NEMA 5-15p male plug for supplying 115V power to the 1/3 hp motor.
- The unit has 1/4 inch male connections for secure fitting of hoses.
- It has a fan and condenser for maximising efficiency with shorter cycle times.
- The unit features 2 easy to read gauges for checking the refrigerant pressures quickly and a comfortable handle to carry the unit to the desired location.
- It comes with an instruction manual for referring to correct procedures & steps of refrigerant recovery.
Compatible Accessories:
- Robinair 100343 Filter / Dryer: Users can install these filter / dryer units at the inlet fitting for removing contaminants / moisture from the incoming refrigerants in the system being serviced.
Standards and Approvals:
Frequently Asked Questions:
Q. How to set up this Robinair RG3 refrigerant recovery machine?
A.
- Firstly, place the machine on a stable surface.
- Install a clean filter screen or filter / dryer to the inlet fitting.
- Connect a hose from the liquid port of the recovery cylinder into the outlet fitting on the unit.
- Connect a hose from the outlet port of a manifold gauge set to the inlet fitting on the unit through the filter / dryer.
- Connect a hose from the selected system's liquid side to the liquid (low pressure) side of the manifold gauge set.
- Connect a hose from the system's vapour side to the vapour (high) side of the manifold gauge set.
- Close all the inlet & outlet valves and place the cylinder on a weighing scale to prevent its overfilling.
Q. What type of cylinders are required for use with this Robinair RG3 refrigerant recovery machine?
A.
- The selected cylinder should be an authorised, refillable refrigerant storage cylinder specs.
- Robinair recommends using 400 psi (27.6 bar) cylinders or at least a 350 psi (24.1 bar) cylinder.
- Closed cylinders should be filled up to 80% of their volume to prevent personal injury & equipment damage.
- Recovery cylinders & filter / dryers should be used with only one refrigerant type.
- Refrigerant cylinders should be stored in a cool, dry place.
Q. What is the push / pull procedure in this recovery machine?
A. Push / pull procedure in this Robinair RG3 refrigerant recovery machine is used to recover refrigerants from large systems containing bulk liquids over 15 lb. Users should follow the push / pull method as described in the unit's instruction manual.